Data centre server room with ESD resin floor
Resin Flooring Systems/Data Centres & Electronics

Resin Flooring for Data Centres

ESD-compliant, seamless resin systems for data centres, server rooms, and electronics facilities — protecting critical infrastructure from electrostatic discharge and providing a controlled, hygienic environment.

Protecting Critical Infrastructure from the Ground Up

Data centres and electronics facilities require flooring that does far more than provide a durable walking surface. Electrostatic discharge (ESD) poses a direct threat to servers, networking equipment, and electronic components — a single uncontrolled discharge can cause immediate failure or latent damage that manifests weeks later. The floor is the primary path to earth for static charges generated by personnel and equipment.

We specify ESD resin flooring systems for data centres and electronics facilities based on the specific resistance requirements of the application — from dissipative systems for general IT environments to fully conductive systems for the most sensitive electronics manufacturing. Every installation is tested and certified to IEC 61340 standards.

Why Data Centres Specify ESD Resin Flooring

ESD Protection

Correctly specified ESD resin systems provide a controlled path to earth for static charges, preventing the build-up of electrostatic potential that can damage sensitive equipment and infrastructure.

IEC 61340 Compliance

Our ESD systems are installed with a copper earthing grid and tested to IEC 61340-4-1 and IEC 61340-5-1 standards, providing documented compliance for audit and insurance purposes.

Seamless, Particle-Free Surface

Seamless resin floors eliminate the particle generation associated with raised access floor tiles and standard floor coverings — maintaining the controlled environment required for sensitive equipment.

Raised Access Floor Compatibility

ESD resin systems can be installed under raised access floors, providing ESD protection at the structural slab level while maintaining compatibility with the raised floor system above.

Chemical Resistance

Resistance to the cleaning chemicals and disinfectants used in data centre environments, maintaining ESD performance over the long term.

Live Environment Installation

We have extensive experience installing ESD resin flooring in live data centre environments — with detailed method statements, dust control, and phased installation programmes that protect operational equipment.

Compliance & Certification

Data centre ESD resin floors are specified and tested to international ESD standards. We provide full test certificates, installation documentation, and ongoing testing programmes to maintain compliance.

  • IEC 61340-4-1 — ESD flooring test methods
  • IEC 61340-5-1 — ESD protection requirements for electronics
  • ANSI/ESD S20.20 — ESD control programme requirements
  • EN 1081 — electrical resistance of resilient floor coverings
  • Uptime Institute Tier certification compatibility
Case Study

Case Study: Tier III Data Centre

📍 London Docklands📐 1,200 m²🔧 Conductive epoxy ESD system with copper earthing grid
Challenge: A colocation data centre operator required ESD flooring for a new data hall build. The specification required a resistance to earth of 25kΩ–1MΩ (dissipative range) throughout the data hall, with a conductive system (< 1MΩ) in the UPS and battery rooms. Installation had to be completed before the raised access floor installation.
Solution: Dissipative epoxy ESD system with 20mm copper earthing grid at 1.2m centres throughout the data hall. Conductive epoxy system in UPS and battery rooms. Full IEC 61340 testing on completion with certificates provided for the client's Tier III certification submission.
Result: IEC 61340 compliance achieved on first test. Tier III certification obtained without floor-related non-conformances. The client has since specified the same system for two further data hall expansions.

Recommended Systems for Data Centres

Dissipative ESD Epoxy

25kΩ–1GΩ resistance range for data halls, server rooms, and general IT environments.

Learn more

Conductive ESD Epoxy

< 1MΩ resistance for UPS rooms, battery rooms, and high-sensitivity electronics areas.

Learn more

Hygienic Seamless Finish

Non-porous, particle-free surfaces for controlled data centre environments.

Learn more

Chemical-Resistant Coatings

Resistance to data centre cleaning chemicals and disinfectants.

Learn more

Get a Free Quote

ESD & data centre specialists

We respond to all enquiries within one business day.

Discuss Your Data Centre Flooring Project

IEC 61340 certified · Free site surveys · UK, USA & Dubai